Hydraulics & Pumps

VFDs on Pumps and Fans: Affinity Laws and Energy-Saving Calculation

Why a 20 % speed reduction can cut power by almost half, and how to calculate real savings.

1 min readUpdated: October 22, 2026
VFDs on Pumps and Fans: Affinity Laws and Energy-Saving Calculation

Photo: Philipp Michel Reichold · CC BY-SA 4.0 · Image credits

The affinity laws

QuantityRelation to speedAt 80 % speed
Flow QQ ∝ N80 %
Head HH ∝ N²64 %
Power PP ∝ N³51 %
Table 1 — Affinity laws for centrifugal pumps and fans

Power varies with the cube of speed, so a small speed reduction produces a large energy saving. Throttling a valve, in contrast, merely adds pressure drop and wastes energy across the valve.

02040608010020406080100Flow (% of rated)Power (% of rated)VFDThrottle valveBypass
Figure 1 — Power for a system with 20 % static head. The curves are typical and depend on the pump curve.

Worked savings example

Example
A 30 kW pump running 6000 h/year at 70 % average flow: ≈ 25 kW with a throttle valve and ≈ 12.4 kW with a VFD. Saving ≈ 12.6 kW, or about 76 MWh per year (≈ 6057 USD at 0.08 USD/kWh).

When a VFD is not suitable

  • Pumps with very high static head (over 60 %): savings shrink and speed must not fall below a minimum.
  • Loads that are nearly constant and always close to rated.
  • Old motors with weak insulation and no dv/dt filter.
Installation tip
Set a minimum speed for motor cooling and seal lubrication (usually 30–40 %) and program skip frequencies to avoid resonance.
Ask me