Control & Instrumentation

The 4–20 mA Current Loop: Principles, Wiring and Troubleshooting

Why it has been the industrial signal standard for over half a century, and how to design it properly.

2 min readUpdated: October 22, 2026
The 4–20 mA Current Loop: Principles, Wiring and Troubleshooting

Photo: JanBurg · CC BY-SA 4.0 · Image credits

Why current, not voltage?

In a series loop the current is identical everywhere, so voltage drop on a long cable or contact resistance does not change the signal. That is why current transmission is far more robust than voltage over hundreds of metres in noisy plants.

Why does it start at 4 mA? (Live zero)

Zero percent of the process is represented by 4 mA, not 0 mA. A 0 mA signal then clearly means a broken wire or failure, and a 2-wire transmitter can power itself from the 4 mA.

I (mA) = 4 + 16 × (PV − LRV) / (URV − LRV)

048121620240246810Measured pressure (bar) — range 0 to 10Loop current (mA)NAMUR low alarm ≤ 3.6NAMUR high alarm ≥ 214–20 mA signal
Figure 1 — Loop current for a 0–10 bar pressure transmitter and the NAMUR NE43 alarm thresholds

Loop burden

The transmitter needs a minimum voltage (typically 12 V). The rest of the supply may drop across cable resistance and the PLC input:

R_max = (V_supply − V_min) / 0.020 A

0200400600800100012001400Max loop resistance (Ω)15015 V30018 V60024 V120036 V
Figure 2 — Maximum total loop resistance (cable + input + barrier) for a 12 V minimum transmitter voltage

Comparison with other standards

StandardNoise immunityCable lengthFault detectionTypical use
4–20 mAExcellentUp to kilometresYes (live zero)Transmitters, actuators
0–10 VMediumTens of metresNoPanels, buildings
1–5 VMediumTens of metresYesLegacy DCS
HARTExcellentAs 4–20 mAYes + diagnosticsSmart transmitters
Table 1 — Comparison of common analog signal methods

Quick troubleshooting

  • 0 mA: broken wire, blown fuse or no supply.
  • Below 3.6 mA: the transmitter is signalling a fault (low alarm).
  • Above 21 mA: sensor failure or short (high alarm).
  • Fluctuation: double earthing or unshielded cable beside power cables.
Tip
Ground the cable shield at one end only (panel side) to avoid creating a ground loop.
Ask me